SATEC EM133 is a multifunction power meter, ideal for a wide range of applications such
as revenue metering, industrial power monitoring and for interfacing SCADA in utility
substations.The EM133 can be fitted with a wide range of communication interfaces and I/O
extensions, making it a cost-effective combination of a power meter, smart transducer and
PLC controller. MID certified for revenue metering, it is designed for DIN-rail mounting,
equipped with built-in communication ports, digital I/Os and anti-tamper enclosures.
Power Meter | |
---|---|
Voltage, current (including neutral current), power, energy, power factor, frequency, voltage/current unbalance | |
Ampere/Volt demand meter | |
25, 50, 60 and 400 Hz measurements | |
Sampling frequency: 128 samples per cycle |
Revenue Meter | |
---|---|
Class 0.5/0.5S accuracy per ANSI C12.20 / IEC 62053-22 | |
Optional: MID certified, Class B or C (EN50470-3); 5A input is mandatory | |
Four-quadrant import and export (e.g. PV), active and reactive energy poly-phase static meter | |
Three-phase total and per phase energy measurements; active, reactive and apparent energy counters | |
Time-of-Use, 4 totalization and tariff energy/demand registers x 8 tariffs, 4 seasons x 4 types of days, 8 tariff changes per day | |
Easily programmable tariff calendar schedule | |
Automatic daily energy and maximum demand profile log for total and tariff registers | |
Sealable, revenue grade anti-tamper design |
I/O | |
---|---|
MEASURING RANGE | |
2 Digital Inputs | 1 form A digital output (Solid State Relay) |
Modular I/O (available options) | |
4 Digital Inputs + 2 digital outputs (SSR or EM) | 12 Digital Inputs + 4 Digital Outputs (including additional com port of choice) |
8 Digital Inputs | 4 Analog Outputs (for Smart Transducer application) |
Harmonic Analyzer | |
---|---|
Voltage and current THD, TDD and K-Factor, | |
Voltage and current harmonic spectrum and angles, up to the 40th order harmonics |
Display | |
---|---|
2 x 16 Characters LCD display; adjustable update time | |
Auto-scroll option with adjustable page exposition time; auto-return to a default page |
Real Time Clock | |
---|---|
Built-in clock and calendar functions | |
2 year battery backup |
Programmable Logical Controller | |
---|---|
Embedded programmable controller | |
16 control set points; programmable thresholds and delays | |
Relay output control (for alarm and protection) | |
1-cycle response time |
Communication Ports | |
---|---|
Built-in | |
Standard 2-wire RS-485 (optional: built-in Dual Port RS485) | |
Add-on Com Modules (1 per device) | |
Multipurpose RS-232/422/485 port | ETH 10/100Base-T |
PROFIBUS | 2G/3G/4G modem |
Wi-Fi module |
Communication Protocols | |
---|---|
Modbus RTU/TCP | |
ASCII | |
DNP 3.0/TCP | |
EC 60870-5-101/104 |
Meter Security | |
---|---|
Three-level Password security for protecting meter setups and accumulated data from unauthorized changes | |
Anti-tamper design (wiring seal) |
Mounting | |
---|---|
DIN Rail sealable connection |
Power Supply | |
---|---|
Self-powered from measured voltage (120/207 – 277/480V AC, L-N/L-L) | |
Auxiliary AC/DC power supply (85-265V AC, 88-290V DC) | |
Special versions (12, 24-48V DC) |
Data Logger | |
---|---|
Non-volatile memory for timestamped event and data logging: over 90 days for 2 daily TOU records, half-hourly writing of 4 parameters and recording over 200 events | |
Event recorder for logging internal diagnostic events and setup changes | |
Two data recorders; programmable data logs on a periodic basis |
Variable Current Inputs | |
---|---|
5A (mandatory for MID) | |
1A | |
HACS: special 40mA inputs for SATEC’s High Accuracy Current Sensors | |
63A Direct Measurement | |
RS5: Special 5A input for 5A clip-on HACS for retrofit installation on existing MV/HV CT secondary. |
Voltage Measurement Input Rating | |
---|---|
Nominal voltage: 400/690V AC (L-N/L-L) | |
Operating range: 15-480/828V AC (L-N/L-L) |
No application images found.