Satec Power Meters

Portable Power Quality Analyzer - EDL180

Portable Analyzer

  • IEC 61000-4-30 Class A

  • IEC 62053-22

  • icon
  • icon
  • icon
  • icon

Portable (Class A, Ed. 3) PQ Analyzer

The EDL180 is a portable version of the Class A (Edition 3) PM180 power quality analyzer,
which holds extensive track record serving as the platform for power quality monitoring
systems in worldwide national grids.Equipped with a 24V battery for backup power supply
andflexible current clamps, it is fitted in a lightweight traveling bag for convenient handling

Benefits & Features

  • Power quality EN50160 reports
  • GOST 32144 reports
  • Waveform capture and event recording @ 256 samples/cycle
  • Built-in: RS485; ETH; IRIG-B
  • Optional ports: 2G/3G

Technical Specifications

Power Meter
Power: True RMS volts, amps, power, power factor, neutral current, angles and unbalance for voltage and current, frequency, symmetrical components and many more
Event and parameter data-logging
Sampling frequency: up to 256 samples/cycle
Power Quality
NMI certified for Class A, Edition 3, per IEC 61000-4-30
EN50160 / GOST 32144 monitoring, statistics & reports
Event statistics complimented by waveform recording in 8 channels (4 voltage inputs, 4 current inputs) @ 256 samples/cycle
V-I angle, THD, TDD and K factor for Voltage and Current and up to the 63rd order harmonic; individual harmonics for V, I, P, Q
Including directional power harmonics (Load or Source)
Inter-harmonics
Disturbance Direction Detection (upstream/downstream)
Flicker according to IEC 61000-4-15
Logging, Recording & Programming
Programmable controller: up to 64 control setpoints, up to 8 conditions OR, AND, arithmetical functions logic, extensive triggers, programmable thresholds and delays, relay control, event-driven data recording
9 fast waveform recorders: simultaneous 8-channel AC, one DC
Waveform sampling rate 32, 64, 128 or 256 samples per cycle
Up to 3.5 min. of continuous waveform recording
16 fast Data Recorders (16 parameters on each data log): From ½ cycle RMS to 2 hour RMS envelopes; programmable data logs on a periodic basis and on internal or external trigger
½-cycle response time
32 digital internal counters
16 internal programmable timers (½ cycle to 24 hours)
Current Inputs
3V AC: inputs for generic current clamps (Rogowski)
Voltage Measurement Inputs
Nominal voltage 690V AC
Operating range up to 828V AC
5th AC/DC voltage input up to 300V DC (monitoring substation battery)

Communication interfaces
Built-in
RS-485
USB
ETH 10/100Base-T
IRIG-B
Optional/additional: (1 per device)
3G GSM; incl. 2nd RS485 port

Modbus

Communication Protocols
Modbus
ASCII
DNP 3.0
IEC 60870-5-101/104
IEC 61850
Display
Graphic color display: 5.7″ touchscreen
Real-Time Clock & Synchronization
Real-Time Clock with maximum 5 seconds drift per month @ 25°C
Provides 1 msec time resolution via IRIG-B time code input or satellite clock for common time base (requires IRIG-B module)
As an SNTP client, it can accept periodic synchronization of the meter clock from an SNTP server
Power Supply
85-265V AC / 88-290V DC
Installed UPS backup: over 4 hours of work at full consumption
Enhanced Meter Security
3 levels Password security for protecting meter setups and accumulated data from unauthorized changes
Defining up to 20 users in different access levels
HACS: special 40mA inputs for SATEC’s High Accuracy Current Sensors
Extra-complex password is required
Access and configuration log is automatically and continuously recorded, documenting all user activity

In Application

No application images found.