Satec Power Meters

Power Quality Analyzer - PM175

EN50160 Power Quality Analyzer

  • IEC 62053-22

  • EN 61000-4-2

  • icon
  • icon
  • icon
  • icon

EN50160 Power Quality Analyzer

The PM175 is an analyzer providing the full range of power quality monitoring and
reporting, according to the EN50160 standard.*
Equipped with built-in digital I/Os and a serial communication interface supporting
SCADA-driven protocols, it is suitable for integration in utility substation or
industrial SCADA systems. Its powerful LED 7-segment display shines visibly in the
darkest environments, facilitating a quick reading of crucial power parameters on-site.
Likewise, it is equipped with a LED load-bar, enabling the viewing of load percentage
at a glance.

The PM172 offers capabilities for basic power quality monitoring, providing calculations such as harmonics,
THD, TDD and K-factor.Its powerful LED 7-segment display shines visibly in the darkest environments,
facilitating the quick reading of crucial power parameters on-site. Likewise, it is equipped with a color
LED load-bar, enabling the viewing of load percentage at a glance.

Benefits & Features

  • EN50160 reports
  • GOST 32144 reports
  • Waveform capture and event recording
  • Built-in : RS485
  • Optional ports: ETH; 2G/3G; Profibus
  • Open protocol: Modbus RTU; DNP3.0; Profibus
  • 5A or 1A
  • 40mA for HACS CTs (100-3,000A)
  • special input: clip-on 5A HACS for retrofit
  • ABB tested and approved
  • 20-650A
  • 200-4,000A

Technical Specifications

Accuracy
Class 0.2S per IEC 62053-22

Class 0.2 per IEC 61557-12
Power Meter
Power: True RMS volts, amps, power, power factor, neutral current, angles and unbalance for voltage and current, frequency, symmetrical components and many more
Event and parameter data-logging
Sampling frequency: 128 samples per cycle
Power Quality
EN50160 / GOST 32144 monitoring, statistics & reports

Event statistics complimented by waveform recording
in 6 channels (3 voltage inputs, 3 current inputs) @ 128 samples/cycle
Voltage and current harmonics and THD coefficients up to the 50th order harmonic
Directional power harmonics
Flicker according to IEC 61000-4-15
Data Logger
Time-of-Use (TOU), 8 totalization and tariff energy/demand registers x 8 tariffs, 4 seasons x 4 types of days, 8 tariff changes per day, easy programmable tariff schedule
Event recorder for logging internal diagnostic events and setup changes
16 data recorders; programmable data logs on a periodic basis and on any internal and external trigger
Variable Current Inputs
5A
1A
HACS: special 40mA inputs for SATEC’s High Accuracy Current Sensors
RS5: special 5A input for 5A clip-on HACS for retrofit installation on existing MV/HV CT secondary.

ABB Sensor Interface (see below)

Voltage Measurement Inputs

Available options:
120V AC Nominal voltage
690V AC Nominal voltage
Built-in I/O
2 Digital Outputs: 3A/250 VAC; 3A/30 VDC; 2 contacts (SPST Form A)
2 Digital Inputs: (dry contact; 15V Internal power supply)
ABB MV Sensor Interface
These sensors are compatible with MV power systems rated up to 24kV. Specific sensors tested by ABB for compatibility with the PM174 in the following current ranges:
20-650A

200-4,000A
Current sensors
Type KECA 80 Cxxx (C104, C165, C184, C216, C260)

KECA 80 C85/td>

KECA 80 D85
Voltage sensors
type KEVA 17,5B20, 5B21

type KEVA 24B20, 24B21
type KEVA 24C10, 24C21, 24C22, 24C23, 24C24, 24C25, 24C26, 24C30
type KEVA 24C10c 24C21c, 24C22c, 24C23c, 24C24c, 24C25c, 24C26c; “c” stands for Metal coated (conductive surface)
KEVA 24C2 4.1
KEVA 24C2 4.1c; “c” stands for Metal coated (conductive surface)
Combined voltage and current sensors
KEVCY 24 RE1

KEVCD A. Sensor name codes : KECVD 12 AE3, KEVCD 17.5 AE3 , KECVD 24 AE3.

Communication interfaces
Built-in
RS-485
RS-232/422
Optional/additional: (1 per device):
ETH 10/100Base-T

PROFIBUS
2G/3G/4G modem
Additional I/O
4 Digital I/O
2 Digital Inputs + 2 Digital Outputs
2 Analog Inputs available rating:
±1mA

0-20mA
0-1mA
4-20mA
2 Analog Outputs available rating:
±1mA

0-20mA
0-1mA
4-20mA
0-5mA
±5mA
Programmable Logical Controller
Embedded programmable controller
16 control set points; programmable thresholds and delays
Relay output control (for alarm and protection)
½-cycle response time
Display

3-row (2×4 characters + 1×6 characters) bright LED display, adjustable update time,
auto-scroll option with adjustable page exposition time, auto-return to a default page
LED bar graph showing percent load with respect to user-definable nominal load current
Detachable display module with a 3-wire RS-485 interface; up to 1000 meters operation
Real Time Clock
Built-in clock and calendar functions
2 year battery backup
Communication Protocols

Modbus
ASCII
DNP3.0
Profibus
Power Supply
9.6-19V DC
19-37V DC
37-72V DC
Meter Security
3 levels Password security for protecting meter setups and accumulated data from unauthorized changes
Mounting
92X92mm square
4’’ round cutout
DIN-rail mounting

In Application