Satec Power Meters

High Accuracy Power Meter - PM172

Advanced Power & Revenue Meter

  • IEC 62053-22

  • EN 61000-4-2

  • icon
  • icon
  • icon
  • icon

Power & Revenue Meter

The PM172 is a Class 0.2S/0.2 power meter designed for high-accuracy metering of three-phase AC circuits. Equipped with built-in digital I/Os and supporting numerous communication protocols, it is suitable for integration in utility substations or industrial SCADA systems.

The PM172 offers capabilities for basic power quality monitoring, providing calculations such as harmonics, THD, TDD and K-factor.Its powerful LED 7-segment display shines visibly in the darkest environments, facilitating the quick reading of crucial power parameters on-site. Likewise, it...

Benefits & Features

Revenue Meter:

  • Class 0.2/0.2S per ANSI C12.20 / IEC 62053-22
  • can bill 3 individual single phase clients...

Communication

Technical Specifications

Accuracy
Class 0.2 per IEC 61557-12
Class 0.2 per ANSI C12.20
Power Meter
Power: True RMS volts, amps, power, power factor, neutral current, angles and unbalance for voltage and current, frequency, symmetrical components and many more
Event and parameter data-logging
Sampling frequency: 128 samples per cycle
Revenue Meter
Exceeds accuracy class 0.2 / 0.2S
Built-in Time of Use (TOU) tariffs to meet any billing requirements
Box-sealed option
Power Quality
Event statistics complimented by waveform recording in 6 channels (3 voltage inputs, 3 current inputs) @ 128 samples/cycle
Individual voltage and current harmonics up to the 63rd order harmonic
Voltage and current THD, TDD & K-Factor
Total Harmonic Powers
Total Harmonic Energies<<
Variable Current Inputs
5A
1A
HACS: special 40mA inputs for SATEC’s High Accuracy Current Sensors
RS5: Special 5A input for 5A clip-on HACS for retrofit installation on existing MV/HV CT secondary.
Voltage Measurement Inputs
Available options:
120V AC Nominal voltage
690V AC Nominal voltage
Programmable Logical Controller
Embedded programmable controller
16 control set points; programmable thresholds and delays
Relay output control (for alarm and protection)
½-cycle response time
Communication interfaces
Built-in
RS-485
RS-232/422
Optional/additional: (1 per device):
ETH 10/100Base-T
PROFIBUS
Built-in I/O
2 Digital Outputs: 3A/250 VAC; 3A/30 VDC; 2 contacts (SPST Form A)
2 Digital Inputs: (dry contact; 15V Internal power supply)
Additional I/O
4 Digital I/O
2 Digital Inputs + 2 Digital Outputs
2 Analog Inputs available rating:
±1mA
0-20mA
0-1mA
4-20mA
2 Analog Outputs available rating:
±1mA
0-20mA
0-1mA
4-20mA
0-5mA
±5mA
Power Supply Default: 85-265V AC / 88-290V DC
9.6-19V DC
19-37V DC
37-72V DC
Mounting
92X92mm square
14’’ round cutout