The PM135 is a multifunctional three-phase power meter.
Featuring versatile I/O options, communication ports and protocols, it is
ideal for integration in utility substations or industrial SCADA systems.
An LCD display, accompanied by a LED load-bar, enables easy on-site access
to power parameters and viewing of load percentage at a glance.
Accuracy | |
---|---|
Class 0.5/0.5S accuracy per ANSI C12.20 / IEC 62053-22 | |
Class 0.2 per IEC 61557-12 |
Power Meter | |
---|---|
Voltage, current (including neutral current), power, energy, power factor, frequency, voltage/current unbalance | |
Ampere/Volt demand meter | |
25, 50, 60 and 400 Hz measurements | |
Sampling frequency: 128 samples per cycle |
Variable Current Inputs | |
---|---|
5A | |
1A | |
HACS: special 40mA inputs for SATEC’s High Accuracy Current Sensors | |
Shunt compatibility for DC metering | |
RS5: Special 5A input for 5A clip-on HACS for retrofit installation on existing MV/HV CT secondary. |
Harmonic Analyzer | |
---|---|
Voltage and current THD, TDD and K-Factor, | |
Voltage and current harmonic spectrum and angles, up to the 40th order harmonic |
Modular I/O | |
---|---|
4 Digital Inputs + 2 digital outputs (SSR or EM) | |
12 Digital Inputs + 4 Digital Outputs (including additional com port of choice) | |
8 Digital Inputs | |
4 Analog Outputs (for Smart Transducer application) |
Programmable Logical Controller | |
---|---|
Embedded programmable controller | |
16 control set points; programmable thresholds and delays | |
Relay output control (for alarm and protection) | |
1-cycle response time |
Communication Protocols | |
---|---|
Modbus RTU/TCP | |
ASCII | |
DNP 3.0/TCP | |
IEC 60870-5-101/104 |
Power Supply | |
---|---|
Auxiliary multi-purpose AC/DC power supply (85-265V AC, 88-290V DC) | |
Special versions (12, 24-48V DC) |
Meter Security | |
---|---|
Three-level Password security for protecting meter setups and accumulated data from unauthorized changes. |
Display | |
---|---|
3×2” / 76x49mm backlit LCD display | |
Adjustable display brightness and update rate | |
Auto-scroll option with adjustable page; autoreturn to a default page | |
LED bar-graph displaying load as percentage of | |
nominal load current (user-definable) |
Programmable Logical Controller | |
---|---|
Embedded programmable controller | |
16 control set points; programmable thresholds and delays | |
Relay output control (for alarm and protection) | |
1-cycle response time |
Power Supply | |
---|---|
Auxiliary multi-purpose AC/DC power supply (85-265V AC, 88-290V DC) | |
Special versions (12, 24-48V DC) |
Communication Interfaces | |
---|---|
Built-in: | |
Standard 2-wire RS-485 | |
Add-on Com Modules (1 per device): | |
Multipurpose RS-232/422/485 port | |
ETH 10/100Base-T | |
PROFIBUS | |
Wi-Fi module |
Real Time Clock & TOU | |
---|---|
Clock and calendar functions | |
Time-of-Use billing and logging: | |
4 totalization and tariff energy/demand registers x 8 tariffs, 4 seasons x 4 types of days, 8 tariff changes per day | |
2 year battery backup |
Mounting | |
---|---|
92×92mm square | |
4” round cutout |
Current Input Rating Options | |
---|---|
5A for CT secondary | |
1A for CT secondary | |
40mA input for HACS remote CTs | |
RS5: 5A split core HACS remote sensor (50/60Hz only) |