Alarm Annunciators (Model AL-701 and AL-702) are microprocessor based. These can be used with various annunciation sequences selectable at site. All inputs to these alarm alarm annunciators are optically isolated. Model AL-701 can have up-to 72 input channels while Model AL-702 has fixed 8 channel input.

Full technical details on our alarm annunciators and possible annunciation sequences are a given on this page. 

 
Model  Features 

Alarm Annunciator
Model AL-701


Image of Alarm Annunciator (Model AL-701)

  • Microprocessor based alarm annunciators 
  • Ideal for use in fertilizer plants , steel plants , petrochemicals , paper industries and other process industries 
  • Alarm Annunciation sequence can be selected at site ( available sequences are listed below )
  • Maximum number of input channels - 64
  • Front and back hinged door
  • High noise immunity
  • All inputs are optically isolated
  • Plug in cards for control , channel and power supply
  • Alarm windows can be filament lamp or LED lamp based
  • Trickle current for heating of filament lamps
  • Alarm window size can be 70X 35 mm or 55 X 30 mm
  • Fault input - NO or NC  can be set individually for each channel via jumpers on the  channel card
  • Interrogation voltage - 12V DC
  • Three control switch inputs  for TEST , ACCEPT and RESET 
  • Hooter control relay output , 1 CO, 5 Amps, 230 VAC , non -inductive
  • Control switches and Electronic Hooter ( with volume control ) available as accessories
  • All connections via terminals on rear of the alarm annunciator 
  • Power supply : 110V AC or 230 VAC  ±10%, 50 Hz.
  • Maximum operating temperature : 50 °C max.
  • Panel mounting
  • Size depends on the configuration of the alarm annunciator 

Brochure on AL701

Mini - Alarm Annunciator
Model AL-702 

Image of Alarm Annunciator (Model AL-702)

  • Microprocessor based alarm annunciator 
  • Eight alarm windows
  • Ideal for use in fertilizer plants , steel plants , petrochemicals , paper industries and other process industries 
  • Low cost
  • Alarm Annunciation sequence can be selected at site ( available sequences are listed below )
  • Eight input channels
  • High noise immunity
  • All inputs are optically isolated
  • LED based alarm windows 
  • Fault input - NO or NC  can be set individually for each channel via jumpers on the  channel card
  • Interrogation voltage - 12V DC
  • Three control switch inputs  for TEST , ACCEPT and RESET 
  • Hooter control relay output , 1 CO, 5 Amps, 230 VAC , non -inductive
  • Control switches and Electronic Hooter ( with volume control ) available as accessories
  • All connections via terminals on tear of the alarm annunciators
  • Power supply : 110V AC or 230 VAC  ±10%, 50 Hz.
  • Maximum operating temperature : 50 °C max.
  • Flush panel mounting
  • Panel Cutout : 184 (H)X 92(W) mm
  • Overall size : 192(H) X 96(W) X 200(D) mm

Brochure on AL702

Alarm Annunciation Sequences

Three alarm annunciation sequences given below are provided in all the alarm annunciators . The required sequence can be selected at site. ( Other sequences can also be provided on request ).

AUTO RESET SEQUENCE (AL7102) - Lock in feature for momentary faults.
Fault Input Action Lamp Output Relay
Normal - Off Off
Fault - Flash On
Fault Accept Steady Off
Normal - Off Off
Normal Before Accept - Flash On
Normal Accept Off Off
Normal Test Flash On
MANUAL RESET SEQUENCE  ( AL7201) Manual Reset , Basic sequence . 
Fault Input Action Lamp Output Relay
Normal - Off Off
Fault - Flash On
Fault Accept Steady Off
Fault Reset Steady Off
Normal - Steady Off
Normal  Reset Off Off
Normal Before Accept - Flash On
Normal Accept Steady Off
Normal Reset Off Off
Normal Test Flash On

FIRST IN MANUAL RESET SEQUENCE (AL7301)  First in fault can be distinguished before ACCEPT by FAST   flash ( subsequent steady ON). 

Fault Input  Action Lamp  Output Relay
First            Subsequent First           Subsequent
Normal      Normal - Off              Off Off
Fault          Normal - Fast Flash   Off On
Fault          Fault - Fast Flash   Slow Flash On
Fault          Fault Accept Fast Flash   Steady Off
Fault          Fault  Reset Fast Flash   Steady Off
Normal      Normal  - Fast Flash   Off Off
Normal      Normal Reset Off             Off Off
Normal   Before Accept      Normal Before  Accept  - Fast Flash   Slow Flash On
Normal     Normal Accept Fast Flash  Off Off
Normal     Normal Reset Off             Off Off
Normal     Normal Test Steady        Steady On